Phoenix Contact – ESSENTIAL-PS/3AC/24DC/240W/EE – Power supply – 1018291
Primary-switched ESSENTIAL edition power supply for DIN rail mounting, input: 3-phase, output: 24 V DC / 240 W
Technical data
Input data
AC operation
|
Nominal input voltage range |
2x / 3x 400 V AC … 500 V AC |
|
Input voltage range |
3x 320 V AC … 575 V AC |
|
Input voltage range AC |
3x 320 V AC … 575 V AC |
|
2x 360 V AC … 575 V AC (for 2-phase operation) |
|
|
Voltage type of supply voltage |
AC |
|
Inrush current |
< 15 A |
|
Inrush current integral (I2t) |
0.2 A2s |
|
AC frequency range |
45 Hz … 65 Hz |
|
Mains buffering time |
> 20 ms (3x 400 V AC) |
|
Current consumption |
3x 0.6 A (400 V AC) |
|
3x 0.5 A (480 V AC) |
|
|
Nominal power consumption |
284.4 VA |
|
Protective circuit |
Transient surge protection; Varistor |
|
Power factor (cos phi) |
0.59 |
|
Typical response time |
< 1 s |
|
Permissible backup fuse |
B6 B10 B16 |
|
Recommended breaker for input protection |
6 A … 16 A |
|
Discharge current to PE |
< 3.5 mA |
Output data
|
Efficiency |
88.5 % (at 400 V AC and nominal values) |
|
Output characteristic |
U/I |
|
Nominal output voltage |
24 V DC ±1 % |
|
Setting range of the output voltage (USet) |
22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
|
Nominal output current (IN) |
10 A (UOUT= 24 V DC) |
|
Derating |
55 °C … 70 °C (2.5 %/K) |
|
Feedback voltage resistance |
35 V DC |
|
Protection against overvoltage at the output (OVP) |
< 35 V DC |
|
Max. capacitive load |
unlimited |
|
Active current limitation |
approx. 15 A |
|
Control deviation |
< 1 % (change in load, static 10 % … 90 %) |
|
< 2 % (change in load, dynamic 10 % … 90 %) |
|
|
< 0.1 % (change in input voltage ±10 %) |
|
|
Residual ripple |
< 10 mVPP |
|
Short-circuit-proof |
yes |
|
Output power |
240 W |
|
Peak switching voltages nominal load |
< 30 mVPP |
|
Maximum no-load power dissipation |
7.5 W |
|
Power loss nominal load max. |
34 W |
|
Rise time |
< 2 ms (UOUT(10 % … 90 %)) |
|
Connection in parallel |
yes, for redundancy and increased capacity |
|
Connection in series |
yes |
Connection data
Input
|
Connection method |
Screw connection |
|
Conductor cross section, rigid min. |
0.2 mm² |
|
Conductor cross section, rigid max. |
2.5 mm² |
|
Conductor cross section flexible min. |
0.2 mm² |
|
Conductor cross section flexible max. |
2.5 mm² |
|
Conductor cross section AWG min. |
24 |
|
Conductor cross section AWG max. |
14 |
|
Stripping length |
9 mm |
|
Screw thread |
M2,5 |
|
Tightening torque, min |
0.4 Nm |
|
Tightening torque max |
0.5 Nm |
Output
|
Connection method |
Screw connection |
|
Conductor cross section, rigid min. |
0.2 mm² |
|
Conductor cross section, rigid max. |
2.5 mm² |
|
Conductor cross section flexible min. |
0.2 mm² |
|
Conductor cross section flexible max. |
2.5 mm² |
|
Conductor cross section AWG min. |
16 |
|
Conductor cross section AWG max. |
12 |
|
Stripping length |
9 mm |
|
Screw thread |
M2,5 |
|
Tightening torque, min |
0.4 Nm |
|
Tightening torque max |
0.5 Nm |
Signaling
|
Types of signaling |
LED |
|
Operating voltage display |
Green LED |
Signal output
|
Status display |
"DC OK" LED green |
|
Note on status display |
UOUT> 21.5 V: LED lights up |
Electrical properties
|
Number of phases |
3 |
|
Insulation voltage input/output |
3 kV AC (type test) |
|
1.5 kV AC (routine test) |
|
|
Insulation voltage output / PE |
500 V DC |
Product properties
|
Product type |
Power supply |
|
Product family |
ESSENTIAL POWER |
|
MTBF (IEC 61709, SN 29500) |
> 700000 h |
Insulation characteristics
|
Protection class |
I (with PE connection) |
|
Overvoltage category |
III |
|
Degree of pollution |
2 |
Dimensions
|
Dimensional drawing |
![]() |
|
Width |
60 mm |
|
Height |
130 mm |
|
Depth |
152.5 mm |
Installation dimensions
|
Installation distance right/left |
0 mm / 0 mm |
|
Installation distance top/bottom |
50 mm / 50 mm |
Mounting
|
Mounting type |
DIN rail mounting |
|
With protective coating |
no |
Material specifications
|
Housing material |
Metal |
Environmental and real-life conditions
Ambient conditions
|
Degree of protection |
IP20 |
|
Ambient temperature (operation) |
-25 °C … 70 °C (> 55 °C Derating: 2.5 %/K) |
|
Ambient temperature (storage/transport) |
-40 °C … 85 °C |
|
Climatic class |
3K3 (in acc. with EN 60721) |
|
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
|
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
|
Vibration (operation) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
|
15 Hz … 150 Hz, 2.3g, 90 min. |
Standards and regulations
|
Standard – Electrical safety |
EN 60950-1 |
|
Standard – Safety extra-low voltage |
EN 60950-1 (SELV) |
|
Approval – requirement of the semiconductor industry with regard to mains voltage dips |
SEMI F47 – 0706 (200 V AC) |
Approvals
|
CSA |
CSA-C22.2 Nr. 107.1-01 |
|
CSA-C22.2 Nr. 60950-01 |
|
|
UL approvals |
UL/C-UL listed UL 508 |
Conformity/Approvals
|
SIL in accordance with IEC 61508 |
0 |
|
Performance level according to ISO 13849 |
without |
EMC data
|
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
|
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
|
EMC requirements for noise emission |
EN 61000-6-3 |
|
EN 61000-6-4 |
|
|
EMC requirements for noise immunity |
EN 61000-6-1 |
|
EN 61000-6-2 |
Noise emission
|
Standards/regulations |
EN 55011 (EN 55022) Class B |
Electrostatic discharge
|
Standards/regulations |
EN 61000-4-2 |
Electrostatic discharge
|
Contact discharge |
8 kV (Test Level 4) |
|
Discharge in air |
8 kV (Test Level 3) |
|
Comments |
Criterion A |
Electromagnetic HF field
|
Standards/regulations |
EN 61000-4-3 |
Electromagnetic HF field
|
Frequency range |
80 MHz … 1 GHz |
|
Test field strength |
10 V/m |
|
Frequency range |
1 GHz … 2 GHz |
|
Test field strength |
10 V/m |
|
Frequency range |
2 GHz … 3 GHz |
|
Test field strength |
10 V/m |
|
Comments |
Criterion A |
Fast transients (burst)
|
Standards/regulations |
EN 61000-4-4 |
Fast transients (burst)
|
Input |
4 kV (Test Level 4 – asymmetrical) |
|
Output |
4 kV (Test Level 4 – asymmetrical) |
|
Signal |
2 kV (Test Level 3 – asymmetrical) |
|
Comments |
Criterion A |
Surge voltage load (surge)
|
Standards/regulations |
EN 61000-4-5 |
Surge voltage load (surge)
|
Input |
2 kV (Test Level 3 – symmetrical) |
|
4 kV (Test Level 4 – asymmetrical) |
|
|
Output |
1 kV (Test Level 2 – symmetrical) |
|
2 kV (Test Level 3 – asymmetrical) |
|
|
Comments |
Criterion A |
Conducted interference
|
Standards/regulations |
EN 61000-4-6 |
Conducted interference
|
Frequency range |
0.15 MHz … 80 MHz |
|
Comments |
Criterion A |
|
Voltage |
10 V (Test Level 3) |
Voltage dips
|
Standards/regulations |
EN 61000-4-11 |
Emitted interference
|
Standards/regulations |
EN 61000-6-3 |
|
Radio interference voltage in acc. with EN 55011 |
EN 55011 (EN 55022) Class B, area of application: Industry and residential |
|
Emitted radio interference in acc. with EN 55011 |
EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria
|
Criterion A |
Normal operating behavior within the specified limits. |
|
Criterion B |
Temporary impairment to operational behavior that is corrected by the device itself. |
Commercial data
|
Item number |
1018291 |
|
Packing unit |
1 pc |
|
Minimum order quantity |
1 pc |
|
Sales key |
CMP |
|
Product key |
CMB333 |
|
GTIN |
4055626502632 |
|
Weight per piece (including packing) |
1,500 g |
|
Weight per piece (excluding packing) |
1,464 g |
|
Customs tariff number |
85044095 |
|
Country of origin |
CN |








Reviews